Turbidity: 5 Nephelometric turbidity
units (N.T.U.) Total Suspended Solids:
10 milligrams per liter
(mg/L) - maximum pH: 6.5 - 9.5 Color: None Hardness: 6 grains per
gallon (g.p.g.) or 102
parts per million (p.p.m.) Iron: 0.3 milligrams per
liter (mg/L) - maximum Manganese: 0.05
milligrams per liter
(mg/L) - maximum Ultraviolet
Transmission: 80%
through one centimeter -
minimum
For Wastewater
Applications
Biological Oxygen
Demand:
30 milligrams per liter
(mg/L) - maximum Total Suspended Solids:
30 milligrams per liter
(mg/L) - maximum Ultraviolet Transmission
at 254 nanometers: 65%
through one centimeter -
minimum
* Other water quality
applications may be
treated by ultraviolet.
Contact one of our
ultraviolet specialists.
***
The Megatron�
Model M250 has been
verified by The Environmental Technology
Verification Program�.
To learn more about the Environmental
Technology Verification Program�
visit: www.epa.gov/etv
ETV ReportETV
Statement
Megatron�,
Ster-L-Ray�
and Easy-Off�
Retainer Cap are
trademarks of the
Atlantic Ultraviolet
Corp.
Copyright 1995-2021 All rights reserved. The information and recommendations contained in this publication are
based upon data collected and are believed to be correct. However, no guarantee or warranty of any
kind, expressed or implied, is made with respect to the information contained herein. Specifications and information are subject to change without notice.